System No. C-AJ-1642 Metallic pipe in solid wall or floor
- Copper pipes, steel pipes, iron pipes or steel conduits up to 4 in. diameter
- F-Rating: 2 h; T-Rating: 1/4 h
- Max. diameter of opening is 5 in.
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 2-1/4 in.
- Optional: Steel sleeve grouted into floor or wall
System information
Test norm | UL 1479 |
Approval Number | C-AJ-1642 |
Seal type | Pipe penetration seal |
System components
Designation | Art. no. | PU |
---|---|---|
ZZ® 365 Fire Protection Sealant | B15V12-0001 | 1 |
Detailed information
- Downloads
- Description
- Copper pipes, steel pipes, iron pipes or steel conduits up to 4 in. diameter
- F-Rating: 2 h; T-Rating: 1/4 h
- Max. diameter of opening is 5 in.
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 2-1/4 in.
- Optional: Steel sleeve grouted into floor or wall