System No. C-AJ-3330 Cables in solid wall or floor
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 45% cable fill in opening of max. 4 in. diameter
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 1-1/4 in.
- Optional: Steel sleeve grouted into floor or wall
System information
Test norm | UL 1479 |
Approval Number | C-AJ-3330 |
Seal type | Mixed penetration seal |
System components
Designation | Art. no. | PU |
---|---|---|
ZZ® 365 Fire Protection Sealant | B15V12-0001 | 1 |
Detailed information
- Downloads
- Description
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 45% cable fill in opening of max. 4 in. diameter
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 1-1/4 in.
- Optional: Steel sleeve grouted into floor or wall