ZZ® M30
Mixed penetration seal or cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables and optical fibre cables, conduits, as well as combustible and non-combustible pipes.
System information
Test norm | EN 1366-3 |
Approval Number | ETA-11-0206 |
Fire resistance class | E, EI |
Fire resistance duration [min] | 60, 90, 120 |
Seal type | Mixed penetration seal, Cable penetration seal, Pipe penetration seal |
Seal opening | angular, round, unregular |
approved components | flexible wall, rigid wall, rigid floor |
System components
Designation | Art. no. | PU | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
ZZ® 230-144 Fire Protection Block show variants
| ||||||||||
ZZ® 330 Fire Protection Foam Starter-Kit | B16N00-0125 | 1 | ||||||||
ZZ® 330 Fire Protection Foam, 6pc.-set | B15VP1-0004 | 60 | ||||||||
ZZ® 330 Fire Protection Foam | B15V06-0001 | 1 | ||||||||
ZZ® 451-150 Fire Protection Wrap | B04N00-0004 | 1 | ||||||||
ZZ® 430-110 Fire Protection Collar | B16N01-0003 | 1 | ||||||||
ZZ® 430-160 Fire Protection Collar | B16N01-0004 | 1 | ||||||||
Identification Plate ETA | B16H00-0051 | 1 |
Detailed information
- Description
Mixed penetration seal or cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables and optical fibre cables, conduits, as well as combustible and non-combustible pipes.
- Additional Information
Suitable for - Fast and easy sealing of openings
- Openings with many penetrating elements
- Openings that are difficult to access or that are irregular
- Easy retroactive-installation
- Single-product solution
- Fast and clean work
Approved penetrating elements - Sheathed electrical cables, telecommunication cables, optical fibre cables up to an outer diameter of 80 mm
- Tied cable bundles up to a total diameter of 100 mm, consisting of sheathed electrical cables, telecommunication cables, optical fibre cables with a maximum outer diameter of 21 mm (sealing of the interstices between cables is not necessary)
- Non-sheathed electrical cables up to a maximum outer diameter of 24 mm
- Individual lines of steel or plastic conduits for control purposes up to a pipe outer diameter of 16 mm
- Cable support systems (cable trays, cable racks, cable ladders) made of steel profiles can be routed through the penetration seal
- P-HD ducts for fibre optic or copper cables (speedpipes), up to Ø 12 mm each and bundles up to Ø 80 mm
- Plastic conduits up to an outer diameter of 63 mm, bundles of multiple pipes up to an outer diameter of 100 mm
- Combustible pipes (without additional fire protection collars) with a pipe outer diameter up to 110 mm and pipe wall thicknesses from 1.8 mm to 12.3 mm
- Pipes of steel, stainless steel, cast steel and copper with a pipe outer diameter up to 88.9 mm and pipe wall thicknesses from 1.0 mm to 14.2 mm, pipes up to a diameter of 28 mm can optionally be sealed without insulation
- Pipes of steel, stainless steel and cast steel with an outer pipe diameter of up to 168.3 and pipe wall thickness from 2.6 mm to 14.2 mm. Pipes of steel, stainless steel and cast steel up to an outer diameter of 35 mm can optionally be sealed without insulation.
- Insulation of non-combustible pipes, consisting of mineral wool shells (density ≥ 90 kg/m³) can either be routed through the penetration seal or can end on the surface of the sealing system
- Rubber insulation AF Armaflex of non-combustible pipes can be routed through the penetration seal
- Non-combustible pre-insulated metal pipes for air conditioners, heating and sanitary systems of type “WICU® Flex”, “WICU® Frio”, “WICU® Clim”, “WICU® Eco”, “Tubolit® Split” and “Tubolit® DuoSplit” with PE or PUR insulation can be fed through the penetration seal (areas of application, insulation thicknesses and possibly additional ZZ® 451 Fire Protection Wrap).
- Sealing system thicknesses from 100 mm depending on the penetrating element and fire resistance classes
- Combination possibility with ZZ® 230 Fire Protection Block in areas free of penetrating elements within the through penetration firestop system
Maximum dimensions in rigid wall width x height [mm] 450x500 Maximum dimensions in flexible wall width x height [mm] 450x500 Maximum dimensions in rigid floor width x height [mm] 450x450